GW-7557-B
Introduction
The GW-7557 Gateway is specially designed for the slave device of PROFIBUS DP protocol. It allows the PROFIBUS master to access the HART slave devices. These HART slave devices may be a transmitter, an actuator, a current output device and so forth. In addition, we also provide the utility software for users to configure the GW-7557. By using this module, users can put their HART slave devices into PROFIBUS network very easily.
PROFIBUS to HART Gateway – ICP DAS
Key Features
- Protocol Support: PROFIBUS DP-V0 slave device with automatic baud rate detection
- HART Integration: Supports 4 HART channels, point-to-point and multi-drop modes, short/long frames, and burst mode
- Dual HART Masters: Allows two HART masters per channel
- High Isolation: 3000 VDC isolation on PROFIBUS side, 2500 Vrms bus-to-logic protection
- Compact Design: DIN-rail mountable with dimensions of 72 x 33 x 119 mm
- Utility Software: Provided for easy configuration and integration
Specifications
- CPU: 80186, 80 MHz or compatible
- Memory: 16 KB EEPROM, 512 KB Flash, 512 KB SRAM
- Watchdog Timer: Built-in
- LED Indicators: PWR, RUN, ERR
- COM Port: RS-232, 3-pin terminal block, up to 115200 bps
- HART Ports: 4 channels, supports up to 15 HART modules per channel
- PROFIBUS Controller: Profichip VPC3+C
- Transceiver: ADI ADM2486
- Baud Rates: PROFIBUS: 9.6k to 12M; COM Port: up to 115.2k
- Power Consumption: 2.0 W
- Operating Temperature: -25°C to +75°C
- Storage Temperature: -30°C to +85°C
- Humidity: 5% to 95% RH, non-condensing
- Installation: DIN-Rail